Common Fault of Transformer and Treatment
I. Voltage Transformer
1. If a voltage transformer has one of the following errors, it shall be stopped at once:
(1) HV fuse is fused twice continuously (10kV voltage transformer);
(2) Internal heat and temperature is too high;
(3) There is a discharge "crackling" sound or other noise inside;
(4) Empyreumatic odor, smoke or fire inside;
(5) The casing is severely ruptured and discharged, and there is spark discharge among the casing, the lead and the shell;
(6) GIS transformer has air leakage or SF6 gas pressure is lower than the minimum operating pressure;
2. When serious errors above are found in voltage transformer, treatment procedures and general troubleshooting solutions are:
(1) Exit the protective and automatic devices which may have mal-operation, and disconnect secondary switch of the faulty voltage transformer (or pull secondary fuse).
(2) Disconnect the isolation switch to isolate error if HV fuse is not fused and insulation on HV side is not broken.
(3) When HV fuse is not fused, but the voltage transformer has serious error and HV insulation side is broken, it is prohibited to use the isolation switch or take down the fuse to disconnect the faulty voltage transformer. The error can only be removed with a circuit breaker,, and disconnect the isolation switch without power, and then restore power supply.
(4) After the isolating of errors and paralleling of primary bus, connect secondary switch of the voltage transformer and put into the protection and automatic devices again.
(5) Extinguish fire via 1211 fire extinguisher
3. Treatment of fusing of primary fuse for the 10kV voltage transformer:
(1) Symptoms: voltage of fusing phase decreases or approaches zero, voltage of phase in good condition remains unchanged or slightly decreases, and indication of active and inactive power meters decreases.
(2) Treatment: disconnect the isolation switch of the voltage transformer, remove the LV fuse , take safety measures, and inspect and make sure there is no external error, then change primary fuse of the same specification. If continuous fusing occurs during power transmission, the transformer many have internal fault. Therefore, the voltage transformer shall be stopped.
4. Treatment of fusing of secondary fuse for the 10kV voltage transformer:
(1) Symptoms:
1) Voltage circuit disconnection signal of the voltage transformer shows, and alarm bell rings.
2) The faulty phase voltage is zero or low, indication of active and inactive power meters is zero or low.
(2) Treatment:
1) Check whether the protector of secondary voltage circuit is fused or has poor contact.
2) If it is not the problem of the protector, report it to the dispatcher on duty instantly.
3) Check whether the voltage loop has loose connection or disconnection.
4) If the cause cannot be found and the error cannot be eliminated, conduct power outage check immediately.
5. Accident handling of the 110kV voltage transformer:
The 110kV and above voltage transformers have no fuse protection on the primary side, and the secondary side uses the LV automatic switch to disconnect the short circuit current of the secondary circuit.
JLSZW-35W THREE-PHASE FOUR-WIRE COMBINATION TYPE TRANSFORMER OUTDOOR
JLSZW6-10 COMBINATION TYPE INSTRUMENT TRANSFORMER
JLSZV-35W THREE-PHASE THREE-WIRE COMBINATION TYPE TRANSFORMER OUTDOOR
JLSZV-20W THREE-PHASE THREE-WIRE COMBINATION TYPE TRANSFORMER OUTDOOR
JLSZV-6、10W OUTDOOR THREE-PHASE THREE-WIRE COMBINATION TYPE TRANSFORMER OUTDOOR
JLSZV-6、10 JLSZV-6、10G JLSZC-6、10R FULLY-ENCLOSED INDOOR THREE-PHASE COMBINATION TYPE TRANSFORMER
JLDZ1-6、10R FULLY-ENCLOSED INDOOR SINGLE-PHASE COMBINATION TYPE TRANSFORMER WITH FUSE
KDG-0.3、0.4/6、10 MINE EXPIOSION-PROOF VACUUM SWITCH CONTROL TRANSFORMER
DG-1、2、3、4/6、10 SINGLE-PHASE CONTROL TRANSFORMER
JDZXW-35 JDZXW3-35 JDZXW4-35 FULLY-ENCLOSED OUTDOOR SINGLE—PHASE VOLTAGE TRANSFORMER
DZW-35 JDZXW-35G JDZW-35R JDZXW-35RG FULLY-ENCLOSED OUTDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZW-20 JDZXW-20G JDZW-20R JDZXW-20RG Outdoor single-phase CURRENT TRANSFORMER
DZW-3、6、10 JDZXW-3、6、10G JDZW2-3、6、10 JDZW-3、6、10R OUTDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZV16-35R FULLY-ENCLOSED INDOOR THREE-PHASEVOLTAGE TRANSFORMER
JDZX16-35R1 JDZX16-35R2 FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER With Fuse
JDZX9-35R FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZX9-35Q JDZX9-35C JDZX9-35D FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZ16-35R JDZX16-35RG FULLY-ENCLOSED SINGLE-PHASE VOLTAGE TRANSFORMER WITH FUSE
JDZ9-27.5Q JDZ9-35Q JDZX9-35G JDZ9-35G FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZX9-15、20Q FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZ9-15、20Q JDZX9-15、20G JDZ9-15、20C JDZX9-15、20CG JDZX9-15、20NG FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JSZW10-3,6,10R, VOLTAGE TRANSFORMER
JSZW-6,10 JSZW-6B,10B VOLTAGE TRANSFORMER
JSZW2-6 JSZW3-6,10 JSZW3-10A JSZW3-10B VOLTAGE TRANSFORMER
JSZVR2-3,6,10X VOLTAGE TRANSFORMER
JSZVR2-3,6,10C VOLTAGE TRANSFORMER
JSZV10-3,6,10R1 VOLTAGE TRANSFORMER
JSZC6-10、6R VOLTAGE TRANSFORMER
JSZFR-3G,6G,10G VOLTAGE TRANSFORMER
JSZF-3G2,6G2,10G2 VOLTAGE TRANSFORMER
JDZXR-3C,6C,10C VOLTAGE TRANSFORMER
JDZXR1-3X,6X,10X JDZXR1-3D,6D,10D JDZXR2-3X,6X,10X JDZXR2-3D,6D,10D VOLTAGE TRANSFORMER
JDZX9-6、10A JDZX9-6、10B JDZX9-6、10Q FULLY-ENCLOSED INDOOR SINGLE-PHASE VOLTAGE TRANSFORMER
JDZX10-6,10 VOLTAGE TRANSFORMER
JDZR10-3,6,10 VOLTAGE TRANSFORMER
JDZ11-3A,6A,10A JDZX11-3,6,10A2 JDZX11-3AG,6AG,10AG JDZ11-3B,6B,10B JDZX11-3BG,6BG,10BG JDZ11-3B2,6B2,10B2 JDZ11-3,6,10JDZ11-3,6,10S VOLTAGE TRANSFORMER
JDZX9-3,6,10 VOLTAGE TRANSFORMER
JDZ-3,6,10R VOLTAGE TRANSFORMER
JDZJ-3,6,10 VOLTAGE TRANSFORMER
JDZ1-6R VOLTAGE TRANSFORMER
LXZK2 CURRENT TRANSFORMER
LXZ1 LXZ2 CURRENT TRANSFORMER
LXK-Ø40 CURRENT TRANSFORMER
LXK CURRENT TRANSFORMER
LXY01-3.0 CURRENT VOITAGE CONVERTER
SDH-0.66 CURRENT TRANSFORMER
LMZJ1-0.5 CURRENT TRANSFORMER
LFZD-1、LMZ□D-1 CURRENT TRANSFORMER
BH-0.66-30A CURRENT TRANSFORMER
BH-0.66 CURRENT TRANSFORMER
LZZW3-35Q CURRENT TRANSFORMER
LZZBJ9-27.5 CURRENT TRANSFORMER
LZZBJ7-35Q CURRENT TRANSFORMER
LZZB9-35D LZZB9-35DG LZZB9-35DJG CURRENT TRANSFORMER
LZZB9-35C CURRENT TRANSFORMER
LZZB9-35A LZZB9-35B CURRENT TRANSFORMER
LZZW1-10Q LZZW2-10Q LZZW3-10Q OUTDOOR CURRENT TRANSFORMER
LMZBW-0.5 CURRENT TRANSFORMER
LZZJ1-10A CURRENT TRANSFORMER
LZZBJ9-10 CURRENT TRANSFORMER
LZZBJ9-10C2Q CURRENT TRANSFORMER
LZZBJ9-10AGY CURRENT TRANSFORMER
LZZB9-10Q CURRENT TRANSFORMER
LMZBJ9-10S CURRENT TRANSFORMER
LMZB6-10Q CURRENT TRANSFORMER
LMZ-10Q CURRENT TRANSFORMER
LMZ-6、10 TWO STAGE CURRENT TRANSFORMER
LDZB6-10 CURRENT TRANSFORMER
LDJ-10 CURRENT TRANSFORMER
©1996-2017 晉ICP備07500050號 Huaxin Copyright
©2016-2017 晉ICP備07500050號 Huaxin Copyright